Platform

All properties, one interface.

Analysis, monitoring and control on six levels, from the organisation down to the individual device. This way one instance can represent a single property as well as a portfolio across several sites.

Sensise platform: building overview of the demo property Villa Marbella with temperature, humidity, CO₂, brightness, window status and three floors

Structure

Six levels for your properties

From the organisation down to the individual device: one instance represents a single property as well as a portfolio across several sites.

Analysis

Analysis of measured values

The platform displays every measured variable a device supplies. You select the period and measured variable and see the history per device, per room or per building section.

Indoor air quality

CO₂, temperature and humidity show how well a room is ventilated. The platform assigns the values to the assessment ranges of ASR A3.6.

  • Share of occupancy time below 1,000 ppm, between 1,000 and 2,000 ppm and above
  • Rooms that are ventilated too rarely stand out immediately in comparison
  • The histories provide data for the ventilation plan and risk assessment
  • High CO₂ levels can lead to tiredness and reduced concentration1
Zone chart of an office: CO₂ level and room temperature over one day, with minimum, average and maximum below

Energy monitoring

Gas, water and electricity meters supply their values continuously. The platform shows consumption per day, week, month and year.

  • Base load, night-time and weekend consumption become visible
  • Heating left running or a leak is spotted before the annual bill arrives
  • Consumption per building forms the baseline for energy management
Consumption view: daily energy values of a meter in September 2026

Check the effect of measures

Two periods can be placed side by side, for example before and after a new control setting or a refurbishment.

  • Comparison per device, per room and per building
  • You can see whether a measure is working or needs adjusting
  • The result can be documented for a committee, management or funding body
Consumption view for the year 2026 with monthly values and selection of a comparison period

What the data delivers in operation

Evidence and reports

Every measured value is stored with a timestamp and can be exported as a CSV file. This provides reports for committees, key figures for energy management under the EnEfG or ISO 50001 and documents for the proof of use.

Detect faults early

Rooms heated around the clock, unusual night-time consumption and moisture at critical points are noticed during ongoing operation, not only with the annual bill.

Prove success

According to the Deutscher Städtetag, low-investment measures save 10 to 20% of annual energy consumption in existing buildings.2 The period comparison shows how much of that reaches your building.

¹ Umweltbundesamt, Richtig Lüften in Schulen · ² Deutscher Städtetag, Einsparung durch Energieverbrauchscontrolling im kommunalen Gebäudebestand, Hinweise Nr. 2.1, March 2025 · The views on this page are redrawn and show sample data.

Monitoring

Monitoring with thresholds and alert levels

Every measured variable can be monitored with its own rules. A rule defines the threshold, alert level and recipients. When the threshold is exceeded, an email goes to the recipients and the alert appears in the property's alert list.

Rules instead of inspection rounds

Instead of walking through rooms, basements and plant areas at regular intervals, you are notified by the platform when something deviates from normal, around the clock and at weekends too.

  • Several rules on the same measured variable, for example a notice from 35 °C and an alarm from 40 °C
  • Availability monitoring: alert when a device stops sending data
  • Battery status per device class, so that batteries are replaced before they fail
  • Leaks, open windows and CO₂ levels from the same devices that also measure and control
  • Counters per alert level for each property, rules can be paused individually
Monitoring rules for a property: nine rules for outdoor temperature, battery status, CO₂, windows, leaks and device availability, each with alert level and number of alerts

Four alert levels

EmergencyAct immediately, for example in case of a water leak
AlarmCheck promptly, for example in case of overheating or device failure
WarningSchedule, for example a low battery
NoticeFor information, for example an open window after hours
Example ruleHow it worksSelected level
Water leakThe leak detector has two states. The rule triggers as soon as it detects water.Emergency
Temperature above 40 °CTwo rules on the same measured variable, with different levels: a notice from 35 °C, an alarm from 40 °C.Alarm
Battery voltageTwo thresholds for two device classes: below 3 V and below 1.5 V.Warning
Window statusOpen or closed. Combined with the history, this becomes the after-hours check.Notice
CO₂ levelThresholds based on the assessment ranges of ASR A3.6: below 1,000 ppm no action, 1,000 to 2,000 ppm ventilate, above 2,000 ppm further measures.Notice
Device availabilityIf a device sends no data for some time, the platform reports it, often before anyone in the building notices.Alarm

Control

Control with schedules per room

Each room follows its own daily profile. The set temperature drops at night, in the evening and as soon as nobody is in the room. When a window is open, the heating stops.

One schedule per control setting

For each control setting you define which set temperature applies from which hour. A separate schedule for the weekend can be added if required.

You then assign the control setting to individual devices, rooms or entire floors. Changes take effect without a site visit.

Schedule of a control setting: 18 °C until 6:00, 22 °C from 6:00 to 18:00, then 18 °C again

Heating control

What the heating control can do

Valve actuators on the radiators control each room according to its schedule.

Setpoint per hourFrom 0:00 to 23:00 as a daily profile
Separate weekend scheduleCan be enabled per control setting
Heating stop when windows are openAs soon as a window contact in the room reports
Setback when unoccupiedAs soon as the presence sensor in the room detects no occupancy
Limited overrideOn the room unit only within a defined range
Adjustable control scopeWhich devices in the room are included in the control
AssignmentTo individual devices, rooms or entire floors
Disable without deletingThe holiday schedule remains in place until next year

Switching actuators

Switching instead of controlling

Some loads only know on and off. They run on a schedule via switching actuators.

Outdoor lightingSwitches on a schedule, independently of the twilight switch
Ventilation systemRuns only during occupancy hours
Circulation pumpOn and off on a schedule
Electric auxiliary heatingThe classic case where a forgotten setting becomes expensive

Administration

Administration of devices, user accounts and permissions

Permissions

Permissions down to room level

  • User accounts and groups per organisation
  • Permission sets instead of fixed roles
  • Visibility and permissions per property, floor and room
  • The facility team sees its own building, management sees all

Devices

Every device has a record

  • Manufacturer, article and location down to the room
  • Last seen, connection status, battery status
  • Measured values with history, log of received messages
  • Configuration, for example transmission interval and thresholds

Integration

What goes out and comes in

  • Export of measurement series as CSV
  • Live values via MQTT to another system
  • Retrieval via the REST API

Operation

Hosted in Germany, GDPR-compliant

Computing power, storage and database are located in a data centre in the Frankfurt area. The certificates and attestations in the table are evidence provided by the data centre operator.

LocationData centre in the Frankfurt area, computing power, storage and database in Germany
Privacy policyGDPR-compliant, with data processing agreement
ISO/IEC 27001, 27017, 27018, 27701Certification of the data centre operator for this location
BSI C5 Type 2Attestation of the data centre operator 01/2026, location within the audit scope
TISAX AL3Evidence of the data centre operator, location within the audit scope
EvidenceAudit reports on request as part of a tender

Get to know the platform in thirty minutes

In the demo we go through a property with fictitious building names: structure, floor view, a time schedule and a threshold rule. Afterwards you will know whether the interface suits your operations.

FAQ

Frequently asked questions about this page

What can the Sensise platform do?

The platform combines five modules: Structure (Organisation, Building, Floor, Room, Zone, Device), analysis of measured values, monitoring with thresholds and alert levels, control with schedules per room, and administration of devices, user accounts and permissions. It runs in the browser, no installation is required. One instance represents a single property as well as a portfolio across several sites.

Where is the data stored and how is it protected?

Computing power, storage and database are located in a data centre in the Frankfurt area, and operation is GDPR-compliant with a data processing agreement. The data is encrypted in transit and at rest. The data centre operator is certified to ISO/IEC 27001, 27017, 27018 and 27701 and holds a BSI C5 Type 2 attestation and TISAX AL3 evidence for the location. We provide the audit reports as part of a tender.

Can the data be passed to a building management system or CAFM?

Yes. The platform exports measurement series as CSV files, sends live values via MQTT and makes them available for retrieval via the REST API, without an additional contract. If you already work with a leading platform, such as a building management system, a CAFM or an energy management system, we pass the data to it.

How does the platform report faults?

Every measured variable can be monitored with its own rules: threshold, alert level and recipients. When the threshold is exceeded, an email goes to the recipients and the alert appears in the property's alert list. There are four alert levels, from Emergency to Notice. A device that stops sending data or a low battery is also reported.

How does heating control via the platform work?

Valve actuators on the radiators control each room according to a daily profile with one setpoint per hour, with a separate weekend schedule if required. When a window is open the heating stops, and when nobody is present it sets back. You assign control settings to individual devices, rooms or entire floors, and changes take effect without a site visit.

How many people can use the platform?

The number of user accounts is unlimited. You assign visibility and permissions via permission sets per property, floor and room. This way the facility team sees its own building and management sees all buildings.

Can we see the platform beforehand?

Yes. In a demo of about thirty minutes we go through a property with fictitious building names: structure, floor view, a time schedule and a threshold rule. We never show building operators' data to anyone.